| Keywords: |
Governor Limit, Limit Violation, Pmin, Pmax, Initial Condition, Limit Checking, Transient Stability |
|
The process of calculating the initial conditions for a transient stability study consist of the following steps:
- Run a normal load flow calculation to determine the steady-state conditions of the network. This result should match the load flow result if motors are not dynamically modeled.
- ETAP then calculates the initial conditions of dynamically modeled generators, exciters, governors, stabilizers, synchronous motors, induction motors, SVCs, HV-DC links, lumped loads, Wind-Turbines, MG Sets, etc.
- During this process, all limits in excitation and governor systems are checked against the calculated initial conditions.
If any limit is exceeded, ETAP will flag the user of the problem.
- For governors, ETAP provides the following message if a governor limit is violated and the calculation stops.
|
|
For most cases, this Error Message is related to the MW generation value (calculated at time t=0) and the "Pmin" and "Pmax" settings of the governor.
|